Frequency manual controller FR-AX
Considering voltage drop of the internal power supply and influence by noise, the wiring length should be 30 m or less. More Details >>
- No:21809
- Release Date:2018/08/22 16:29
-
1. Use the external terminals STF, RL, and SD. (A push-ON switch for operation is required between the terminals STF and SD, and a push-OFF switch is require... More Details >>
- No:21816
- Release Date:2018/08/22 16:29
-
You also need to set Pr.79 (Operation mode) to "3". More Details >>
- No:21844
- Release Date:2018/08/22 16:29
-
The frequency can be set to 65 Hz with the initial setting.Check if Pr.1 (Maximum frequency) is set to 60 Hz. More Details >>
- No:21858
- Release Date:2018/08/22 16:29
-
No. Use a frequency setting potentiometer with the resistance of 1 kΩ and B characteristics.Input voltage is not linear due to the inverter's internal impeda... More Details >>
- No:21911
- Release Date:2018/08/22 16:30
-
You can use it for inverter operation, but the running speed of the inverter does not change linearly with regard to turn of the frequency setting potentiome... More Details >>
- No:21912
- Release Date:2018/08/22 16:30
-
While the FR-PU04 does not display parameter names, it displays parameter numbers and you can set them. More Details >>
- No:21919
- Release Date:2018/08/22 16:30
-
The Radio Act applies to the products used for the purpose of the radio waves. Inverters are used for motor drive and thus out of the scope. More Details >>
- No:20994
- Release Date:2018/08/22 16:25
-
If Pr 27 is not set, the operation starts at the speed of RL. More Details >>
- No:21123
- Release Date:2018/08/22 16:26
-
Check the AU signal (AU - SD). To use the terminal 4, the AU signal (AU - SD) needs to be turned ON. Turning ON the AU signal (AU - SD) disables the terminal 2. More Details >>
- No:21267
- Release Date:2018/08/22 16:26