FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-D700
FAQ
Keyword Search
FAQ within [ FREQROL-D700 ]
-
Since the percent value read by the calibration parameter C7 indicates that the voltage of 10 V is internally detected as 101.0%, use 101.0% as is.If you cha... More Details >>
- No:21740
- Release Date:2018/08/22 16:29
-
The inverter outputs the peak voltage 300 to 400 VDC of the bus voltage not in a pure sine wave but a in a PWM waveform. Check if the lamp to be connected ca... More Details >>
- No:21323
- Release Date:2018/08/22 16:27
-
Number of stations that can be set in FR Configurator
The station numbers that can be set differ depending on the version of FR-Configurator (FR-SW3-SETUP-WJ) setup software. For Ver.2.00 or later, station numbe... More Details >>
- No:21305
- Release Date:2018/08/22 16:26
-
1. Press the PU/EXT key on the operation panel FR-PA07 to choose the PU operation mode. Set Pr.161 (Frequency setting/key lock operation selection) to "1" an... More Details >>
- No:21761
- Release Date:2018/08/22 16:29
-
The forward rotation and reverse rotation are enabled by pressing the FWD/REV key on the operation panel. More Details >>
- No:21364
- Release Date:2018/08/22 16:27
-
FR-PA02 built-in potentiometer
Change Pr.146 (Built-in potentiometer switching) to "0" (built-in frequency setting potentiometer). More Details >>
- No:21862
- Release Date:2018/08/22 16:29
-
Set Pr.40 (RUN key rotation direction selection) to "1" (Reverse). More Details >>
- No:21693
- Release Date:2018/08/22 16:28
-
Operations cannot be enabled separately. You only can disable or enable all the operations. More Details >>
- No:21366
- Release Date:2018/08/22 16:27
-
Normally, the auto tuning condition depends on the combination of the inverter and motor (including wiring to the motor), perform auto tuning each time. The ... More Details >>
- No:21293
- Release Date:2018/08/22 16:26
-
Safety stop function of the FR-D700/FR-E700
It is recommended to install the magnetic contactor on the input side of the inverter for safety. The category 3 can be satisfied without installing it. More Details >>
- No:20837
- Release Date:2018/08/22 16:24
221-230 of Total 260