The FR-DU07 cannot be used with the FR-E700, FR-D700, or FR-F700PJ. More Details >>
- No:21854
- Release Date:2018/08/22 16:29
-
Set Pr.40 (RUN key rotation direction selection) to "1" (Reverse). More Details >>
- No:21693
- Release Date:2018/08/22 16:28
-
Pr.38 of the E500 corresponds to Pr.125 (Terminal 2 frequency setting gain frequency) of D700. Pr.39 of the E500 corresponds to Pr.126 (Terminal 4 frequency ... More Details >>
- No:21254
- Release Date:2018/08/22 16:26
-
The operation panel FR-PA02 for the FR-E500 can be used for these models.You need the FR-E5P (back cover adapter set) and FR-C20□ (connection cable) for the ... More Details >>
- No:21860
- Release Date:2018/08/22 16:29
-
Check if Pr.13 (Starting frequency) is set to higher than 10 Hz.Also check if a signal is input through the terminal MRS. More Details >>
- No:21722
- Release Date:2018/08/22 16:29
-
Checking terminals used:Are the terminals MRS and RES open?Are the terminals STR and SD short-circuited correctly?Is the voltage/current switch of the termin... More Details >>
- No:21916
- Release Date:2018/08/22 16:30
-
Setting dial and FR-PA02 built-in potentiometer
When the FR-PA02 is connected to the inverter with a cable, the FR-PA02 becomes effective.The operation panel of the inverter can also be used to set some pa... More Details >>
- No:21861
- Release Date:2018/08/22 16:29
-
You can do so by setting Pr.73 to "10" or "11". (For A700/F700 (P), supply negative input to the terminal 1.) More Details >>
- No:21908
- Release Date:2018/08/22 16:30
-
The brake unit can be installed. FR-BU2-1.5K and GZG300W50 ? can be used in combination. More Details >>
- No:21332
- Release Date:2018/08/22 16:27
-
When both "Hz" and "A" are turned off, the output voltage monitor is active.The display indicates that the output voltage is 19.5 V. More Details >>
- No:21782
- Release Date:2018/08/22 16:29