  • Rotation speed display

    It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>

    • No:21180
    • Release Date:2018/08/22 16:26
  • PU operation

    Set Pr.79 (Operation mode) to "1" (PU operation mode) and change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21863
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Change Pr.79 (Operation mode) to "3" (Combined operation mode) and short-circuit the external terminals STF and SD (or STR and SD for reverse rotation). More Details >>

    • No:21859
    • Release Date:2018/08/22 16:29
  • Running frequency

    The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>

    • No:21820
    • Release Date:2018/08/22 16:29
  • RUN blinks

    When using the setting dial to set the frequency, turn the dial and press the "SET" key while the desired value flickers. (The value and "F" flicker alternat... More Details >>

    • No:21692
    • Release Date:2018/08/22 16:28
  • FR-PA07

    The forward rotation and reverse rotation are enabled by pressing the FWD/REV key on the operation panel. More Details >>

    • No:21364
    • Release Date:2018/08/22 16:27
  • Proportional band of multiple inverters

    By importing the operation frequency from the AM terminal (analog output) of the first inverter to the FR-FH (ratio setter), the operation command which is p... More Details >>

    • No:21250
    • Release Date:2018/08/22 16:26
  • External multi-speed setting and multi-speed command

    It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>

    • No:21815
    • Release Date:2018/08/22 16:29
  • Parameter

    No parameter can be used to directly set this time.Changing Pr.9 (Electronic thermal O/L relay) changes the time. More Details >>

    • No:21769
    • Release Date:2018/08/22 16:29
  • Terminal FM meter connection

    Check the connection with the meter.If the terminal FM is connected to the positive terminal and the terminal SD is connected to the negative terminal of the... More Details >>

    • No:21762
    • Release Date:2018/08/22 16:29