FAQ within [ FREQROL-D700 ]

31-40 of Total 260

prev 4 / 26page next
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Yes, you can set Pr.20 to 20 Hz. More Details >>

    • No:21683
    • Release Date:2018/08/22 16:28
  • Frequency setting

    You can connect up to three inverters to a single external frequency setting potentiometer to control them.   More Details >>

    • No:21917
    • Release Date:2018/08/22 16:30
  • Output current

    Increasing the value of Pr.0 (Torque boost) increases the output voltage, and the output current also increases.Note that increasing this value too high puts... More Details >>

    • No:21732
    • Release Date:2018/08/22 16:29
  • Terminal FM meter connection

    Check the connection with the meter.If the terminal FM is connected to the positive terminal and the terminal SD is connected to the negative terminal of the... More Details >>

    • No:21762
    • Release Date:2018/08/22 16:29
  • FR-DU07

    Not possible.Instead of FR-DU07, use FR-PA07 (or FR-PU07) as an operation panel for FR-E700. More Details >>

    • No:21708
    • Release Date:2018/08/22 16:29
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27
  • Using external potentiometer and multi-speed operation together

    You can use an external potentiometer and multi-speed operation together.When an external potentiometer signal input and multi-speed setting occur simultaneo... More Details >>

    • No:21920
    • Release Date:2018/08/22 16:30
  • Frequency setting

    You can do so by setting Pr.73 to "10" or "11". (For A700/F700 (P), supply negative input to the terminal 1.) More Details >>

    • No:21908
    • Release Date:2018/08/22 16:30
  • Offline auto tuning

    Auto tuning can be performed because the motor is one rank lower than the inverter capacity. More Details >>

    • No:21351
    • Release Date:2018/08/22 16:27