  • FR-PA07

    The operation command source is automatically transferred to the connected FR-PU07 or FR-PA07. More Details >>

    • No:21700
    • Release Date:2018/08/22 16:28
  • Current setting

    Yes.The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current s... More Details >>

    • No:21770
    • Release Date:2018/08/22 16:29
  • FR-DU07

    The FR-DU07 cannot be used with the FR-E700, FR-D700, or FR-F700PJ. More Details >>

    • No:21854
    • Release Date:2018/08/22 16:29
  • Operation panel (DU04)

    The FR-DU04 can be used in the 700 series inverters, however, some restrictions apply and parameter copy is disabled. More Details >>

    • No:21261
    • Release Date:2018/08/22 16:26
  • Parameter

    Press the "MODE" key on the operation panel several times to display "P.0" and parameter setting screen. Then turn the setting dial to display "C..." screen ... More Details >>

    • No:21336
    • Release Date:2018/08/22 16:27
  • Terminal CS

    FR-E700, D700, and F700PJ do not have the terminal CS and you can only control automatic restart by setting Pr.57 (Restart coasting time). More Details >>

    • No:21707
    • Release Date:2018/08/22 16:29
  • RS-485 communication

    1. You can set Pr.117 for "n1" (Station number) of the FR-S500 for the D700/E700/F700PJ series.2. You can set Pr.338, Pr.339, and Pr.342 for "n8" (Operation ... More Details >>

    • No:21758
    • Release Date:2018/08/22 16:29
  • External installationRated current

    Since the external thermal prevents the motor from being overheated, install it between the output terminal of the inverter and the motor.The rated current i... More Details >>

    • No:21817
    • Release Date:2018/08/22 16:29
  • Coasting

    1. Set Pr.162 to "10" (Frequency search at every start).2. You can ignore the setting if the motor excitation current is unknown. More Details >>

    • No:21718
    • Release Date:2018/08/22 16:29
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29