FAQ within [ FREQROL-D700 ]
-
Basically it is not possible due to the operation command source.However, if Pr.77 (Parameter write selection) is set to "2", you can use both the FR-PA07 an... More Details >>
- No:21698
- Release Date:2018/08/22 16:28
-
There is a priority between the setting dial and multi-speed settings.Since the multi-speed setting is given a higher priority, the setting by the setting di... More Details >>
- No:21702
- Release Date:2018/08/22 16:29
-
FR-E700, D700, and F700PJ do not have the terminal CS and you can only control automatic restart by setting Pr.57 (Restart coasting time). More Details >>
- No:21707
- Release Date:2018/08/22 16:29
-
No. You cannot check the accumulated number of rotations on the monitor. More Details >>
- No:21715
- Release Date:2018/08/22 16:29
-
Check if Pr.13 (Starting frequency) is set to higher than 10 Hz.Also check if a signal is input through the terminal MRS. More Details >>
- No:21722
- Release Date:2018/08/22 16:29
-
The FR-E720S series and D720S series conform to the single-phase 200 V input specifications. More Details >>
- No:21723
- Release Date:2018/08/22 16:29
-
Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>
- No:21729
- Release Date:2018/08/22 16:29
-
Automatic restart after instantaneous power failure setting
You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>
- No:21731
- Release Date:2018/08/22 16:29
-
1. Press the PU/EXT key on the operation panel FR-PA07 to choose the PU operation mode. Set Pr.161 (Frequency setting/key lock operation selection) to "1" an... More Details >>
- No:21761
- Release Date:2018/08/22 16:29
-
Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>
- No:21768
- Release Date:2018/08/22 16:29