FAQ within [ FREQROL-D700 ]

81-90 of Total 260

prev 9 / 26page next
  • Electronic thermal O/L relay setting

    When using multiple motors, connect an external thermal for each of them. Set Pr.9 to "0" to disable the function. (When multiple motors are present, it is n... More Details >>

    • No:21676
    • Release Date:2018/08/22 16:28
  • Brake resistor

    It will be the shared type. More Details >>

    • No:21331
    • Release Date:2018/08/22 16:27
  • Brake resistor

    Use high-duty brake resistor FR-ABR-2.2K. (Shared with the 1.5K inverter.) More Details >>

    • No:21330
    • Release Date:2018/08/22 16:27
  • Operation mode setting

    To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>

    • No:21852
    • Release Date:2018/08/22 16:29
  • Frequency, monitor setting

    Set Pr.52 (PU/DU main display data selection) to "5".Set the monitor as the third monitor, frequency -> current -> setting frequency. More Details >>

    • No:21745
    • Release Date:2018/08/22 16:29
  • Parameter copy of FR-Configurator

    The parameter can be copied to only one inverter. More Details >>

    • No:21306
    • Release Date:2018/08/22 16:26
  • Motor coasting

    To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>

    • No:21271
    • Release Date:2018/08/22 16:26
  • Control terminal

    You also need to set Pr.79 (Operation mode) to "3". More Details >>

    • No:21844
    • Release Date:2018/08/22 16:29
  • FR-PU04

    While the FR-PU04 does not display parameter names, it displays parameter numbers and you can set them. More Details >>

    • No:21919
    • Release Date:2018/08/22 16:30
  • Terminal FM

    No. This is because the current cannot flow if the total internal impedance of the meter connected to the terminal FM is 300 Ω or higher.You can connect mult... More Details >>

    • No:21864
    • Release Date:2018/08/22 16:29