FAQ within [ FREQROL-D700 ]

81-90 of Total 260

prev 9 / 26page next
  • FR-PA02

    The operation panel FR-PA02 requires the optional FR-E5P (control panel rear cover and adapter set) and connection cable FR-CB20□. Check that Pr.146 (Built-i... More Details >>

    • No:21367
    • Release Date:2018/08/22 16:27
  • UL standard

    Both 200 V class and 400 V class are suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 264 V maximum (528 V f... More Details >>

    • No:21358
    • Release Date:2018/08/22 16:27
  • Running frequency

    There are two methods to reduce the running frequency variation. 1. Increase the setting value of Pr.74 (Input filter time constant) to reduce the variation.... More Details >>

    • No:21296
    • Release Date:2018/08/22 16:26
  • Frequency setting

    If Pr.79 (Operation mode) is set to "0" (PU/EXT switching mode), press the PU/EXT button on the operation panel to turn on the PU LED.Turn the setting dial t... More Details >>

    • No:21855
    • Release Date:2018/08/22 16:29
  • Operation mode setting

    To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>

    • No:21852
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This is due to specifications that multi-speed selection is prioritized and setting with the setting dial is ignored.The setting dial is effective when multi... More Details >>

    • No:21843
    • Release Date:2018/08/22 16:29
  • Multi-speed setting and external potentiometer

    The multi-speed setting is prioritized.The external potentiometer setting is effective when the multi-speed signal is not input. More Details >>

    • No:21773
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Check if Pr.13 (Starting frequency) is set to higher than 10 Hz.Also check if a signal is input through the terminal MRS. More Details >>

    • No:21722
    • Release Date:2018/08/22 16:29
  • Saving parameter with FR-Configurator

    When FR Configurator (FR-SW3-SETUP-WJ) is saved as a file from the menu, the extension is "me3". The size of this fie will be large since device settings and... More Details >>

    • No:21311
    • Release Date:2018/08/22 16:26
  • Brake resistor

    The brake resistor is MRS120W200. More Details >>

    • No:21274
    • Release Date:2018/08/22 16:26