  • S-shape acceleration/deceleration of the FR-D700

    It does not change even when General-purpose magnetic flux vector control is performed. Pr.3 is the inflection point of the S-shape. More Details >>

    • No:20834
    • Release Date:2018/08/22 16:24
  • Radio Act

    The Radio Act applies to the products used for the purpose of the radio waves. Inverters are used for motor drive and thus out of the scope. More Details >>

    • No:20994
    • Release Date:2018/08/22 16:25
  • RS-485 and analog input

    The time from when the frequency command is applied until it is reflected on the operation of the motor is different. For the analog input, the multiple anal... More Details >>

    • No:21050
    • Release Date:2018/08/22 16:25
  • Rotation speed display

    It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>

    • No:21180
    • Release Date:2018/08/22 16:26
  • Proportional band of multiple inverters

    By importing the operation frequency from the AM terminal (analog output) of the first inverter to the FR-FH (ratio setter), the operation command which is p... More Details >>

    • No:21250
    • Release Date:2018/08/22 16:26
  • Driving a single-phase motor

    No, it cannot. More Details >>

    • No:21253
    • Release Date:2018/08/22 16:26
  • Parameter read

    By setting Pr.160 (User group read selection ("Extended function display selection" for D700)) to "0", all the parameters can be read. More Details >>

    • No:21262
    • Release Date:2018/08/22 16:26
  • Input phase loss

    The detection time 1 s cannot be changed. More Details >>

    • No:21277
    • Release Date:2018/08/22 16:26
  • Frequency

    When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>

    • No:21284
    • Release Date:2018/08/22 16:26
  • Installation direction

    Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>

    • No:21286
    • Release Date:2018/08/22 16:26