FAQ within [ FREQROL-A700 ]

1-10 of Total 352

prev 1 / 36page next
  • RUN blinks

    Rapid blinking of the RUN LED suggests that the frequency is not set correctly.When the operation mode setting of Pr.79 is changed, the entrance point of the... More Details >>

    • No:21757
    • Release Date:2018/08/22 16:29
  • PS display

    "PS" is displayed when the inverter is stopped with the "STOP/RESET" button from PU. The PU stop (PS) release method is as follows. (1) Release method using ... More Details >>

    • No:21264
    • Release Date:2018/08/22 16:26
  • Frequency setting

    In this case, the JOG operation is prioritized.When the terminals JOG and SD are short-circuited and turned ON, the frequency setting by the external potenti... More Details >>

    • No:21804
    • Release Date:2018/08/22 16:29
  • Error "E.UVT" (undervoltage protection)

    The possible causes of the error UVT are as follows.- Low power supply voltage - Insufficient power supply capacity - Damage or failure Check the power suppl... More Details >>

    • No:21295
    • Release Date:2018/08/22 16:26
  • Cooling fan

    Pr.244 (Cooling fan operation selection) controls turning ON/OFF of the cooling fan and is initially set to "1". When the inverter is powered ON, the cooling... More Details >>

    • No:21670
    • Release Date:2018/08/22 16:28
  • Frequency setting

    Change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21792
    • Release Date:2018/08/22 16:29
  • Parameter copy method of FR-Configurator

    The data can be copied to other inverters. 1. Save the parameter of the inverter to be copied with extension "pr3" by using "export". 2. Replace the connecte... More Details >>

    • No:21307
    • Release Date:2018/08/22 16:26
  • Motor specifications setting

    Yes.Set Pr.19 (Base frequency voltage) to "200 V".200 V output will be obtained during 60 Hz operation. More Details >>

    • No:21717
    • Release Date:2018/08/22 16:29
  • Switching External operation, PU operation

    Setting Pr.79 (Operation mode) to "6" sets the switchover mode. Pressing the "PU/EXT" key on the operation panel during External operation switches the mode ... More Details >>

    • No:21289
    • Release Date:2018/08/22 16:26
  • PU operation

    1. Yes. 2. Set Pr.17 to "2".  3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>

    • No:21359
    • Release Date:2018/08/22 16:27