FAQ


FAQAbout Products

- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A700
FAQ
Keyword Search
FAQ within [ FREQROL-A700 ]
-
Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>
- No:21788
- Release Date:2018/08/22 16:29
-
It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>
- No:21180
- Release Date:2018/08/22 16:26
-
The calibration parameter C6 (Terminal 4 frequency setting bias) is initially set to "20%". Therefore, voltage input to the terminal 4 does not become effect... More Details >>
- No:21806
- Release Date:2018/08/22 16:29
-
Set Pr.3 (Base frequency) and Pr.18 (High speed maximum frequency) to "340 Hz", Pr.19 (Base frequency voltage) to "200 V", Pr.125 (Terminal 2 frequency setti... More Details >>
- No:21789
- Release Date:2018/08/22 16:29
-
Check the setting of Pr.79 (Operation mode).If the setting value is "2", frequency commands from an external terminal is effective and the frequency setting ... More Details >>
- No:21797
- Release Date:2018/08/22 16:29
-
Set Pr.37 (Speed display) to the speed obtained when operating the machine at the frequency set with Pr.505 (Speed setting reference). (For FR-F700/E700/D700... More Details >>
- No:21716
- Release Date:2018/08/22 16:29
-
Connecting ammeter to output side
Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>
- No:21681
- Release Date:2018/08/22 16:28
-
It is not stored in a parameter but memorized as the frequency setting value after acceleration by the acceleration signal.You can also choose whether or not... More Details >>
- No:21733
- Release Date:2018/08/22 16:29
-
The FR Configurator FR-SW3-SETUP-WJ can only allow for test operation.Since this is a tool to support the system launch and maintenance, it is not designed f... More Details >>
- No:21914
- Release Date:2018/08/22 16:30
-
Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>
- No:21768
- Release Date:2018/08/22 16:29
91-100 of Total 352