  • Wiring the terminal

    There is no problem with the wiring. Keep the rating (24 VDC, 0.1 A) of the terminal PC. More Details >>

    • No:21342
    • Release Date:2018/08/22 16:27
  • Brake resistor

    Connect the brake resistor to the terminal P and terminal PR. (For the FR-A700-7.5K or lower, remove the jumper of the terminals PR and PX.) Do not remove th... More Details >>

    • No:21333
    • Release Date:2018/08/22 16:27
  • Frequency setting

    You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>

    • No:21915
    • Release Date:2018/08/22 16:30
  • Frequency setting

    You can use it for inverter operation, but the running speed of the inverter does not change linearly with regard to turn of the frequency setting potentiome... More Details >>

    • No:21912
    • Release Date:2018/08/22 16:30
  • Frequency setting

    You can change the terminal 4 to voltage input. (The terminal 4 is set to the current input terminal at the initial setting.)To change the terminal 4 to volt... More Details >>

    • No:21787
    • Release Date:2018/08/22 16:29
  • Switching between external operation and NET operation

    You can write frequency setting by setting Pr.339 (Communication speed command source) to "0". More Details >>

    • No:21687
    • Release Date:2018/08/22 16:28
  • Switching between external operation and NET operation

    You can monitor the fault output in both NET operation and external operation. More Details >>

    • No:21686
    • Release Date:2018/08/22 16:28
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27
  • Speed command

    Calibrate the terminal 2 bias. More Details >>

    • No:21281
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Check the AU signal (AU - SD). To use the terminal 4, the AU signal (AU - SD) needs to be turned ON. Turning ON the AU signal (AU - SD) disables the terminal 2. More Details >>

    • No:21267
    • Release Date:2018/08/22 16:26