Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>
- No:21768
- Release Date:2018/08/22 16:29
-
Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>
- No:21326
- Release Date:2018/08/22 16:27
-
The detection time 1 s cannot be changed. More Details >>
- No:21277
- Release Date:2018/08/22 16:26
-
Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>
- No:21788
- Release Date:2018/08/22 16:29
-
It is the fixing screw for the inverter cooling fan cover.The size and number of screws depend on the model and capacity.(When exporting the product to the E... More Details >>
- No:21746
- Release Date:2018/08/22 16:29
-
The resistors cannot be used in combination other than described. Operations of brake units and inverters are not verified. When resistors are used in uncert... More Details >>
- No:21328
- Release Date:2018/08/22 16:27
-
It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>
- No:21247
- Release Date:2018/08/22 16:26
-
No. You cannot check the accumulated number of rotations on the monitor. More Details >>
- No:21715
- Release Date:2018/08/22 16:29
-
Switching between external operation and NET operation
You can monitor the fault output in both NET operation and external operation. More Details >>
- No:21686
- Release Date:2018/08/22 16:28
-
Yes. With the setting "66", you can choose NET operation when X66 is ON, and external operation when X66 is OFF. More Details >>
- No:21675
- Release Date:2018/08/22 16:28