FAQ within [ FREQROL-A700 ]

91-100 of Total 351

prev 10 / 36page next
  • Graph function in FR-Configurator

    Even the USB is used, FR Configurator requires at least 50 ms sampling time (for each monitoring item). In this case, since three types of data are monitored... More Details >>

    • No:21310
    • Release Date:2018/08/22 16:26
  • Parameter setting

    Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>

    • No:21270
    • Release Date:2018/08/22 16:26
  • Frequency setting

    You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>

    • No:21915
    • Release Date:2018/08/22 16:30
  • Terminal FM

    Set Pr.56 (Current monitor reference) to "10A". More Details >>

    • No:21865
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Pr.1 (Maximum frequency) or Pr.18 (High speed maximum frequency).   More Details >>

    • No:21805
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Even though the maximum frequency setting is changed using CC-Link, the running frequency is not changed. By writing the set frequency to the remote register... More Details >>

    • No:21346
    • Release Date:2018/08/22 16:27
  • 4 to 20 mA output

    Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>

    • No:21246
    • Release Date:2018/08/22 16:26
  • CC-Link

    Use Pr.542 (Station number). More Details >>

    • No:21876
    • Release Date:2018/08/22 16:29
  • Base frequency setting value

    Set the rated frequency of the motor used to it.  More Details >>

    • No:21814
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Normally, any of the PU, EXT, or NET LED turns ON.Check if the parameter unit FR-PU04/FR-PU07 or operation panel FR-PA07 is externally connected to the PU co... More Details >>

    • No:21803
    • Release Date:2018/08/22 16:29