No. You cannot check the accumulated number of rotations on the monitor. More Details >>
- No:21715
- Release Date:2018/08/22 16:29
-
Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>
- No:21326
- Release Date:2018/08/22 16:27
-
Calibrate C6 (Pr.904) (Terminal 4 frequency setting bias frequency) and C7 (Pr.905) (Terminal 4 frequency setting gain frequency). If the situation does not ... More Details >>
- No:21265
- Release Date:2018/08/22 16:26
-
It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>
- No:21247
- Release Date:2018/08/22 16:26
-
To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>
- No:21799
- Release Date:2018/08/22 16:29
-
Set Pr.52 (DU/PU main display data selection) to "5".This allows for displaying the setting frequency on the voltage monitor.Then, switch to the monitor mode... More Details >>
- No:21784
- Release Date:2018/08/22 16:29
-
This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>
- No:21775
- Release Date:2018/08/22 16:29
-
Use the inverter's calibration parameters Pr.C2/C3, Pr.125/C4 to adjust the bias and gain for each inverter.Connect the wires from the frequency setting pote... More Details >>
- No:21728
- Release Date:2018/08/22 16:29
-
It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>
- No:21785
- Release Date:2018/08/22 16:29
-
The full scale of the frequency is initially set to 60 Hz and the frequency indication becomes the full scale at 60 Hz operation.To change the indication val... More Details >>