For low-speed operation, perform auto tuning and use (Advanced) magnetic flux vector control. More Details >>
- No:21810
- Release Date:2018/08/22 16:29
-
You can do so by setting Pr.339 (Communication speed command source) = 1 (external). More Details >>
- No:21881
- Release Date:2018/08/22 16:29
-
Yes. More Details >>
- No:21713
- Release Date:2018/08/22 16:29
-
Yes. However, write the setting data to the RAM of the inverter.Set RWw1 in the setting value and turn ON the frequency setting command RYD.To continuously s... More Details >>
- No:21825
- Release Date:2018/08/22 16:29
-
1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>
- No:21838
- Release Date:2018/08/22 16:29
-
Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>
- No:21839
- Release Date:2018/08/22 16:29
-
You can use the CC-Link type programming example for the FR-E500 as a reference.In the programming example for the FR-E500, the A series programmable control... More Details >>
- No:21836
- Release Date:2018/08/22 16:29
-
Set Pr.79 (Operation mode) setting value to "0", "2", or "6", Pr.340 (Communication startup mode selection) other than the setting value, Pr.542 (Station num... More Details >>
- No:21896
- Release Date:2018/08/22 16:29
-
The station number and baud rate were set using the dial for the FR-A5NC, but parameter is used for the FR-A7NC. Pr.542 (Communication station number (CC-Lin... More Details >>
- No:21248
- Release Date:2018/08/22 16:26
-
Use the digital output/additional analog output FR-A7AY (E kit). More Details >>