- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A700
FAQ
Keyword Search
FAQ within [ FREQROL-A700 ]
-
First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>
- No:21808
- Release Date:2018/08/22 16:29
-
When Pr.79 is set to "3", the JOG operation is not available by turning ON the terminal JOG.Instead of the JOG function, you can set the low-speed RL of the ... More Details >>
- No:21760
- Release Date:2018/08/22 16:29
-
The resistors cannot be used in combination other than described. Operations of brake units and inverters are not verified. When resistors are used in uncert... More Details >>
- No:21328
- Release Date:2018/08/22 16:27
-
To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>
- No:21271
- Release Date:2018/08/22 16:26
-
Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>
- No:21270
- Release Date:2018/08/22 16:26
-
Normally, Pr.80 and Pr.81 are the parameters that can be changed when the operation is stopped in the PU operation mode. The "Er4" is a mode designation erro... More Details >>
- No:21335
- Release Date:2018/08/22 16:27
-
Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>
- No:21286
- Release Date:2018/08/22 16:26
-
Set Pr.340 (Communication startup mode selection) to "1" or "2".Also, by setting Pr.79 (Operation mode selection) to "0", "2", or "6", the inverter enters th... More Details >>
- No:21879
- Release Date:2018/08/22 16:29
-
Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>
- No:21845
- Release Date:2018/08/22 16:29
-
Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>
- No:21780
- Release Date:2018/08/22 16:29