  • Terminal indicator lamp

    The inverter outputs the peak voltage 300 to 400 VDC of the bus voltage not in a pure sine wave but a in a PWM waveform. Check if the lamp to be connected ca... More Details >>

    • No:21323
    • Release Date:2018/08/22 16:27
  • Model setting in FR-Configurator

    Check the version of FR-Configurator (FR-SW3-SETUP-WJ). If the version is "1.00", it does not support or detect the FR-E740. Version "2.00" supports the FR-E... More Details >>

    • No:21309
    • Release Date:2018/08/22 16:26
  • Parameter setting

    Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>

    • No:21270
    • Release Date:2018/08/22 16:26
  • CC-Link

    Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>

    • No:21839
    • Release Date:2018/08/22 16:29
  • Output current value

    The detection level of the output current value cannot be changed using a potentiometer or a similar device.   More Details >>

    • No:21779
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You need to press the "SET" key with the initial setting.The frequency is not set unless you press the "SET" key.Setting Pr.161 (Frequency setting/key lock o... More Details >>

    • No:21735
    • Release Date:2018/08/22 16:29
  • Output current

    Increasing the value of Pr.0 (Torque boost) increases the output voltage, and the output current also increases.Note that increasing this value too high puts... More Details >>

    • No:21732
    • Release Date:2018/08/22 16:29
  • Megger test

    When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>

    • No:21327
    • Release Date:2018/08/22 16:27
  • Capacity selection

    Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>

    • No:21326
    • Release Date:2018/08/22 16:27
  • Frequency setting signal

    Set C5 (Pr.904) (Terminal 4 frequency setting bias frequency) to 0 Hz and Pr.126 (Terminal 4 frequency setting gain frequency) to 50 Hz. More Details >>

    • No:21268
    • Release Date:2018/08/22 16:26