  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27
  • Rated frequency setting

    Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>

    • No:21280
    • Release Date:2018/08/22 16:26
  • Monitor indicator

    The first priority window of the monitor may be set to the current.When the current is displayed on the monitor (the unit is "A"), press "SET" to switch to t... More Details >>

    • No:21765
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When turning the setting dial to set the frequency, press the "SET" key while the desired value blinks. (The setting frequency and "F" flicker alternately.) More Details >>

    • No:21742
    • Release Date:2018/08/22 16:29
  • Connecting ammeter to output side

    Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>

    • No:21681
    • Release Date:2018/08/22 16:28
  • Operation panel

    If "PS" is displayed even the "STOP/RESET" key on the operation panel is not pressed, a inverter fault may be the cause. In this case, consult with your sale... More Details >>

    • No:21343
    • Release Date:2018/08/22 16:27
  • Electromagnetic contactor

    It is not recommended to start and stop the inverter with the electromagnetic contactor (MC). This will accelerate the deterioration (due to the inrush curre... More Details >>

    • No:21322
    • Release Date:2018/08/22 16:27
  • Connection cable of FR-Configurator

    It is the standardized Mini-B connector. More Details >>

    • No:21312
    • Release Date:2018/08/22 16:26
  • NET mode, external operation switching

    You can switch between the NET mode and external operation.Assign the X66 signal (Operation switching) to an unused terminal for switching.Also, set Pr.79 (O... More Details >>

    • No:21906
    • Release Date:2018/08/22 16:30
  • Frequency setting

    The frequency can be set to 65 Hz with the initial setting.Check if Pr.1 (Maximum frequency) is set to 60 Hz. More Details >>

    • No:21858
    • Release Date:2018/08/22 16:29