  • Frequency meter

    First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>

    • No:21808
    • Release Date:2018/08/22 16:29
  • JOG function

    When Pr.79 is set to "3", the JOG operation is not available by turning ON the terminal JOG.Instead of the JOG function, you can set the low-speed RL of the ... More Details >>

    • No:21760
    • Release Date:2018/08/22 16:29
  • Brake unit

    The resistors cannot be used in combination other than described. Operations of brake units and inverters are not verified. When resistors are used in uncert... More Details >>

    • No:21328
    • Release Date:2018/08/22 16:27
  • Motor coasting

    To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>

    • No:21271
    • Release Date:2018/08/22 16:26
  • Parameter setting

    Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>

    • No:21270
    • Release Date:2018/08/22 16:26
  • Parameter display setting

    Normally, Pr.80 and Pr.81 are the parameters that can be changed when the operation is stopped in the PU operation mode. The "Er4" is a mode designation erro... More Details >>

    • No:21335
    • Release Date:2018/08/22 16:27
  • Installation direction

    Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>

    • No:21286
    • Release Date:2018/08/22 16:26
  • NET operation mode

    Set Pr.340 (Communication startup mode selection) to "1" or "2".Also, by setting Pr.79 (Operation mode selection) to "0", "2", or "6", the inverter enters th... More Details >>

    • No:21879
    • Release Date:2018/08/22 16:29
  • Control terminal

    Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>

    • No:21845
    • Release Date:2018/08/22 16:29
  • Output voltage

    Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>

    • No:21780
    • Release Date:2018/08/22 16:29