FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A700
FAQ
Keyword Search
FAQ within [ FREQROL-A700 ]
-
Pr.30 = "1" and Pr.70 = "0". More Details >>
- No:21143
- Release Date:2018/08/22 16:26
-
No. Check the parameter setting of the A700, and then adjust the parameter setting of the A800 to those of the A700. For the details, refer to the replacemen... More Details >>
- No:21107
- Release Date:2018/08/22 16:25
-
Change Pr.79 (Operation mode) to "3" (Combined operation mode) and short-circuit the external terminals STF and SD (or STR and SD for reverse rotation). More Details >>
- No:21859
- Release Date:2018/08/22 16:29
-
To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>
- No:21852
- Release Date:2018/08/22 16:29
-
Since the operation panels of the E700, D700, and F700PJ do not have keys for the forward (FWD) and reverse (REV) rotations, you can only command rotation in... More Details >>
- No:21841
- Release Date:2018/08/22 16:29
-
1. You can reset the inverter from an external terminal.You can do it without regard to the setting of Pr.338 (Communication operation command source) and Pr... More Details >>
- No:21837
- Release Date:2018/08/22 16:29
-
External multi-speed setting and multi-speed command
It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>
- No:21815
- Release Date:2018/08/22 16:29
-
The error LED on the master side of the programmable controller blinks (faulty station present).According to the SW80 station information, an error flag is a... More Details >>
- No:21813
- Release Date:2018/08/22 16:29
-
Frequency manual controller FR-AX
Considering voltage drop of the internal power supply and influence by noise, the wiring length should be 30 m or less. More Details >>
- No:21809
- Release Date:2018/08/22 16:29
-
Check the setting of Pr.79 (Operation mode).If the setting value is "2", frequency commands from an external terminal is effective and the frequency setting ... More Details >>
- No:21797
- Release Date:2018/08/22 16:29