In this case, the JOG operation is prioritized.When the terminals JOG and SD are short-circuited and turned ON, the frequency setting by the external potenti... More Details >>
- No:21804
- Release Date:2018/08/22 16:29
-
With the automatic bypass sequence (Pr.139 ≠ 9999, Pr.159 = 9999), the motor operation is switched to commercial power supply operation when the output frequ... More Details >>
- No:21189
- Release Date:2018/08/22 16:26
-
Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>
- No:21780
- Release Date:2018/08/22 16:29
-
"n" in the address RWwn indicates a value determined by the station number setting. More Details >>
- No:21867
- Release Date:2018/08/22 16:29
-
The frequency can be set to 65 Hz with the initial setting.Check if Pr.1 (Maximum frequency) is set to 60 Hz. More Details >>
- No:21858
- Release Date:2018/08/22 16:29
-
1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>
- No:21838
- Release Date:2018/08/22 16:29
-
You can use optional items, such as enclosure surface operation panel FR-PA07 and parameter unit FR-PU07.Use the PU connector of the inverter for connection.... More Details >>
- No:21832
- Release Date:2018/08/22 16:29
-
Set Pr.3 (Base frequency) and Pr.18 (High speed maximum frequency) to "340 Hz", Pr.19 (Base frequency voltage) to "200 V", Pr.125 (Terminal 2 frequency setti... More Details >>
- No:21789
- Release Date:2018/08/22 16:29
-
If you try to change a parameter in other than the PU operation mode, the mode specification error "Er4" may occur.Set the parameters in the PU operation mod... More Details >>
- No:21778
- Release Date:2018/08/22 16:29
-
10 VDC voltage from terminal 10
Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>
- No:21727
- Release Date:2018/08/22 16:29