  • Brake resistor

    When the built-in brake resistor is used, the regenerative brake duty is as follows:200 V 0.4K to 3.7K: 3%, 5.5K to 7.5K: 2%400 V 0.4K to 7.5K: 2 % The capac... More Details >>

    • No:21273
    • Release Date:2018/08/22 16:26
  • Brake unit

    The brake unit operates when the bus voltage exceeds the brake operation voltage. More Details >>

    • No:21272
    • Release Date:2018/08/22 16:26
  • Motor coasting

    To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>

    • No:21271
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Set C5 (Pr.904) (Terminal 4 frequency setting bias frequency) to 0 Hz and Pr.126 (Terminal 4 frequency setting gain frequency) to 50 Hz. More Details >>

    • No:21268
    • Release Date:2018/08/22 16:26
  • AM terminal output

    Set Pr.55 (Frequency monitoring reference) of the first inverter to 70 Hz. More Details >>

    • No:21257
    • Release Date:2018/08/22 16:26
  • Proportional band of multiple inverters

    By importing the operation frequency from the AM terminal (analog output) of the first inverter to the FR-FH (ratio setter), the operation command which is p... More Details >>

    • No:21250
    • Release Date:2018/08/22 16:26
  • Electronic bypass function

    The operation cannot be manually switched to the commercial power supply operation at an inverter fault. The operation can be automatically switched to the c... More Details >>

    • No:21191
    • Release Date:2018/08/22 16:26
  • Electronic bypass function

    The signals MRS and CS are required when the automatic bypass sequence enabled. More Details >>

    • No:21187
    • Release Date:2018/08/22 16:26
  • Vector control

    Install the resistor between the terminals PC and OH. More Details >>

    • No:21160
    • Release Date:2018/08/22 16:26
  • Tuning

    Setting the tuning data without tuning makes no difference. The tuning method of the FR-A700 is different from that of V500. Tuning can be performed by setti... More Details >>

    • No:21139
    • Release Date:2018/08/22 16:26