FAQ within [ FREQROL-A700 ]

161-170 of Total 352

prev 17 / 36page next
  • RUN blinks

    When using the setting dial to set the frequency, turn the dial and press the "SET" key while the desired value flickers. (The value and "F" flicker alternat... More Details >>

    • No:21692
    • Release Date:2018/08/22 16:28
  • Adjustment of analog gain

    Use Pr.903 (Frequency setting voltage gain) for setting the FR-E500. For the 700 series, use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (... More Details >>

    • No:21689
    • Release Date:2018/08/22 16:28
  • Frequency setting

    Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>

    • No:21685
    • Release Date:2018/08/22 16:28
  • FR-PA07

    The forward rotation and reverse rotation are enabled by pressing the FWD/REV key on the operation panel. More Details >>

    • No:21364
    • Release Date:2018/08/22 16:27
  • FR-PA07

    The adapter is not necessary. Only the dedicated cable FR-CB20□ is required. More Details >>

    • No:21362
    • Release Date:2018/08/22 16:27
  • PU operation

    1. Yes. 2. Set Pr.17 to "2".  3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>

    • No:21359
    • Release Date:2018/08/22 16:27
  • Operation panel

    If "PS" is displayed even the "STOP/RESET" key on the operation panel is not pressed, a inverter fault may be the cause. In this case, consult with your sale... More Details >>

    • No:21343
    • Release Date:2018/08/22 16:27
  • Pulse change

    When the pulse is counted and displayed, 1440 pulses are output with the frequency of the inverter is 60 Hz. Since these pulses are limited to 2400 pulses, a... More Details >>

    • No:21334
    • Release Date:2018/08/22 16:27
  • Capacity selection

    Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>

    • No:21326
    • Release Date:2018/08/22 16:27
  • Graph function in FR-Configurator

    Even the USB is used, FR Configurator requires at least 50 ms sampling time (for each monitoring item). In this case, since three types of data are monitored... More Details >>

    • No:21310
    • Release Date:2018/08/22 16:26

161-170 of Total 352