FAQ within [ FREQROL-A700 ]
-
It is not activated because the function itself is disabled. More Details >>
- No:21137
- Release Date:2018/08/22 16:26
-
"E.OSD" occurs when the rotation speed is not decreased for one second despite the start command (STF, STR) is turned OFF. More Details >>
- No:21159
- Release Date:2018/08/22 16:26
-
You cannot monitor the running frequency and conveyor speed (machine speed) simultaneously.The inverter does not have a function to output them simultaneously. More Details >>
- No:21827
- Release Date:2018/08/22 16:29
-
Set "33" or "34". More Details >>
- No:21167
- Release Date:2018/08/22 16:26
-
It can be performed by setting Pr.292 (Automatic acceleration/deceleration) to "8" and Pr.279 (Brake opening current) to 0%. More Details >>
- No:21186
- Release Date:2018/08/22 16:26
-
Yes. More Details >>
- No:21713
- Release Date:2018/08/22 16:29
-
Set Pr.9, Pr.71, Pr.80, Pr.81, Pr.83, Pr.84, and Pr.96. More Details >>
- No:21721
- Release Date:2018/08/22 16:29
-
Advanced magnetic flux vector control
When using the geared motor GM-S(B), set Pr.71 to "13" and also set Pr.9, Pr.80, and Pr.81.Perform auto tuning as required. Perform auto tuning as required. ... More Details >>
- No:21756
- Release Date:2018/08/22 16:29
-
Since the Advanced magnetic flux vector control method uses slip compensation to compensate the frequency, the value is not shown as exactly 60 Hz.For V/F co... More Details >>
- No:21807
- Release Date:2018/08/22 16:29
-
For the inverter, the option card FR-A7NC is necessary. More Details >>
- No:21897
- Release Date:2018/08/22 16:29