  • Frequency setting

    The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>

    • No:21800
    • Release Date:2018/08/22 16:29
  • Switching between external operation and NET operation

    You can switch between external operation and NET operation by turning ON/OFF the terminal X66 (RM). You can switch while Pr.79 (Operation mode) is set to "6... More Details >>

    • No:21688
    • Release Date:2018/08/22 16:28
  • Switching External operation, PU operation

    Setting Pr.79 (Operation mode) to "6" sets the switchover mode. Pressing the "PU/EXT" key on the operation panel during External operation switches the mode ... More Details >>

    • No:21289
    • Release Date:2018/08/22 16:26
  • Terminals P1 and P

    Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>

    • No:21921
    • Release Date:2018/08/22 16:30
  • Brake resistor

    Use two resistors for the high-duty brake resistor FR-ABR-15K. (Connect two resistors of 18 ? in parallel.) More Details >>

    • No:21329
    • Release Date:2018/08/22 16:27
  • Reverse rotation prevention selection

    Yes, it does. When the inverter is coasting in the reverse direction, it starts in the reverse direction and switches to the forward rotation after a deceler... More Details >>

    • No:21125
    • Release Date:2018/08/22 16:26
  • Operation panel

    If "PS" is displayed even the "STOP/RESET" key on the operation panel is not pressed, a inverter fault may be the cause. In this case, consult with your sale... More Details >>

    • No:21343
    • Release Date:2018/08/22 16:27
  • NET operation mode

    Normally, the inverter starts up in the NET operation mode at power ON when Pr.340 is set to "10" and Pr.79 is set to "0". When it starts up in the PU operat... More Details >>

    • No:21319
    • Release Date:2018/08/22 16:27
  • Frequency setting

    If Pr.79 (Operation mode) is set to "0" (PU/EXT switching mode), press the PU/EXT button on the operation panel to turn on the PU LED.Turn the setting dial t... More Details >>

    • No:21855
    • Release Date:2018/08/22 16:29
  • Terminal setting

    To use the terminal as voltage input, you need to:- Set Pr.267 (Terminal 4 input selection).- Set the voltage/current input switch on the inverter board.- Se... More Details >>

    • No:21771
    • Release Date:2018/08/22 16:29