  • CC-Link

    You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>

    • No:21905
    • Release Date:2018/08/22 16:30
  • CC-Link

    Set Pr.79 (Operation mode) setting value to "0", "2", or "6", Pr.340 (Communication startup mode selection) other than the setting value, Pr.542 (Station num... More Details >>

    • No:21896
    • Release Date:2018/08/22 16:29
  • CC-Link

    Input 4 words, output 4 words for version 1. 2, 4, and 8 times for version 2. More Details >>

    • No:21874
    • Release Date:2018/08/22 16:29
  • Running frequency

    Check the setting of Pr.1 (Maximum frequency) and Pr.18 (High speed maximum frequency).Pr.1 is initially set to "120 Hz". More Details >>

    • No:21821
    • Release Date:2018/08/22 16:29
  • Minimum frequency

    If any other frequency is not set, when the start signal is input, the inverter starts acceleration from 0.5 Hz set with Pr.13 (Starting frequency) up to 3 H... More Details >>

    • No:21777
    • Release Date:2018/08/22 16:29
  • Frequency, monitor setting

    Set Pr.52 (PU/DU main display data selection) to "5".Set the monitor as the third monitor, frequency -> current -> setting frequency. More Details >>

    • No:21745
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Even while the inverter is operating, you can use the setting dial to change the frequency and then press the SET key and the inverter operates at the new fr... More Details >>

    • No:21739
    • Release Date:2018/08/22 16:29
  • Stop-on-contact control

    Set Pr.270 (Stop-on-contact control) to "1".Set Pr.184 (RES terminal function selection) to "3" to choose the RT signal function.When the terminals RL and RT... More Details >>

    • No:21691
    • Release Date:2018/08/22 16:28
  • Megger test

    When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>

    • No:21327
    • Release Date:2018/08/22 16:27
  • Electromagnetic contactor

    It is not recommended to start and stop the inverter with the electromagnetic contactor (MC). This will accelerate the deterioration (due to the inrush curre... More Details >>

    • No:21322
    • Release Date:2018/08/22 16:27