  • Terminal

    Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>

    • No:21679
    • Release Date:2018/08/22 16:28
  • Network operation

    Yes. With the setting "66", you can choose NET operation when X66 is ON, and external operation when X66 is OFF. More Details >>

    • No:21675
    • Release Date:2018/08/22 16:28
  • FR-PA07

    When Pr.79 is set to "3", since the start command is in the External operation mode, the RUN key of FR-PA07 does not work. More Details >>

    • No:21303
    • Release Date:2018/08/22 16:26
  • Driving a single-phase motor

    No, it cannot. More Details >>

    • No:21253
    • Release Date:2018/08/22 16:26
  • Frequency setting

    You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>

    • No:21915
    • Release Date:2018/08/22 16:30
  • Frequency setting

    Up to 30 m. (To avoid noise and voltage drop)   More Details >>

    • No:21910
    • Release Date:2018/08/22 16:30
  • CC-Link

    Check if the CC-Link wires are short-circuited and/or station numbers are duplicated.   More Details >>

    • No:21891
    • Release Date:2018/08/22 16:29
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • Frequency

    When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>

    • No:21284
    • Release Date:2018/08/22 16:26
  • 4 to 20 mA output

    Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>

    • No:21246
    • Release Date:2018/08/22 16:26