  • Frequency setting

    The calibration parameter C6 (Terminal 4 frequency setting bias) is initially set to "20%". Therefore, voltage input to the terminal 4 does not become effect... More Details >>

    • No:21806
    • Release Date:2018/08/22 16:29
  • Frequency setting

    It is not stored in a parameter but memorized as the frequency setting value after acceleration by the acceleration signal.You can also choose whether or not... More Details >>

    • No:21733
    • Release Date:2018/08/22 16:29
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • External terminal

    1. Use the external terminals STF, RL, and SD. (A push-ON switch for operation is required between the terminals STF and SD, and a push-OFF switch is require... More Details >>

    • No:21816
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can change the terminal 4 to voltage input. (The terminal 4 is set to the current input terminal at the initial setting.)To change the terminal 4 to volt... More Details >>

    • No:21787
    • Release Date:2018/08/22 16:29
  • A7AY

    1. Yes.  2. The standard set by Pr.56. More Details >>

    • No:21669
    • Release Date:2018/08/22 16:28
  • Model setting in FR-Configurator

    Check the version of FR-Configurator (FR-SW3-SETUP-WJ). If the version is "1.00", it does not support or detect the FR-E740. Version "2.00" supports the FR-E... More Details >>

    • No:21309
    • Release Date:2018/08/22 16:26
  • Operation stop, frequency setting

    Set Pr.79 (Operation mode) to "1" (PU operation mode).  More Details >>

    • No:21819
    • Release Date:2018/08/22 16:29
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) to "50 Hz".Set Pr.1 (Maximum frequency) to "50 Hz". More Details >>

    • No:21720
    • Release Date:2018/08/22 16:29