FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A700
FAQ
Keyword Search
FAQ within [ FREQROL-A700 ]
-
Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>
- No:21245
- Release Date:2018/08/22 16:26
-
You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>
- No:21905
- Release Date:2018/08/22 16:30
-
Set Pr.338 (Operation command source) to "1" (external terminal).Set Pr.339 (Speed command source) to "0" (communication).Check the setting of Pr.79 for oper... More Details >>
- No:21869
- Release Date:2018/08/22 16:29
-
Please use the inverter optional FR-A7AY.It supports voltage output (0 to 10 VDC) and current output (0 to 20 mA DC).For the voltage output (0 to 10 VDC), th... More Details >>
- No:21812
- Release Date:2018/08/22 16:29
-
Pr.1 (Maximum frequency) or Pr.18 (High speed maximum frequency). More Details >>
- No:21805
- Release Date:2018/08/22 16:29
-
Yes.The inverter requires the start signal and frequency setting signal. More Details >>
- No:21793
- Release Date:2018/08/22 16:29
-
No parameter can be used to directly set this time.Changing Pr.9 (Electronic thermal O/L relay) changes the time. More Details >>
- No:21769
- Release Date:2018/08/22 16:29
-
Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>
- No:21907
- Release Date:2018/08/22 16:30
-
Even while the inverter is operating, you can use the setting dial to change the frequency and then press the SET key and the inverter operates at the new fr... More Details >>
- No:21739
- Release Date:2018/08/22 16:29
-
When the pulse is counted and displayed, 1440 pulses are output with the frequency of the inverter is 60 Hz. Since these pulses are limited to 2400 pulses, a... More Details >>
- No:21334
- Release Date:2018/08/22 16:27
201-210 of Total 351