FAQ within [ FREQROL-A700 ]

211-220 of Total 351

prev 22 / 36page next
  • Terminal FM

    Set Pr.56 (Current monitor reference) to "10A". More Details >>

    • No:21865
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When the frequency is set using the setting dial, it is not necessary to set it again.The inverter memorizes the setting value internally even after the powe... More Details >>

    • No:21842
    • Release Date:2018/08/22 16:29
  • CC-Link

    Check if the master station uses CC-Link Version 1 and the FR-A7NC uses CC-Link Version 2. More Details >>

    • No:21831
    • Release Date:2018/08/22 16:29
  • Frequency setting

    The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>

    • No:21800
    • Release Date:2018/08/22 16:29
  • Monitor indicator

    Press the "SET" key once while the output frequency is monitored.The unit indicator LED changes from "Hz" to "A" and the monitor display changes to the current. More Details >>

    • No:21764
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Change the value of Pr.18 (High speed maximum frequency).You can set any frequency within the range defined by Pr.18. More Details >>

    • No:21737
    • Release Date:2018/08/22 16:29
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • Wiring length

    The total wiring length is as follows: 100 m + (20 m × 5) = 200m. More Details >>

    • No:21144
    • Release Date:2018/08/22 16:26
  • Sine wave filter

    The sine wave filter can be applied only under V/F control. When Pr.72 PWM frequency selection is set to 25, V/F control is set automatically. The applicable... More Details >>

    • No:21068
    • Release Date:2018/08/22 16:25
  • Frequency setting

    You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>

    • No:21915
    • Release Date:2018/08/22 16:30