  • FR-PA07

    When Pr.79 is set to "3", since the start command is in the External operation mode, the RUN key of FR-PA07 does not work. More Details >>

    • No:21303
    • Release Date:2018/08/22 16:26
  • RS-485 communication

    Blinking of the "RUN" LED on the panel suggests that the frequency command may not be input. Create a frequency setting data as for the forward rotation comm... More Details >>

    • No:21301
    • Release Date:2018/08/22 16:26
  • Auto tuning

    With the monitor indicator "1", there is no problem with the parameter setting of auto tuning. Check if the terminals MRS and SD are not shortened in the wir... More Details >>

    • No:21294
    • Release Date:2018/08/22 16:26
  • Installation direction

    Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>

    • No:21286
    • Release Date:2018/08/22 16:26
  • Input phase loss

    The detection time 1 s cannot be changed. More Details >>

    • No:21277
    • Release Date:2018/08/22 16:26
  • Amount of heat generated

    Refer to the FR-A700/F700/E700/D700 series TECHNICAL MANUAL (section 3.7.2) and the Technical News. The FR-A700/F700/E700/D700 series TECHNICAL MANUAL can be... More Details >>

    • No:21263
    • Release Date:2018/08/22 16:26
  • Parameter read

    By setting Pr.160 (User group read selection ("Extended function display selection" for D700)) to "0", all the parameters can be read. More Details >>

    • No:21262
    • Release Date:2018/08/22 16:26
  • DC reactor

    The 75K or higher DC reactor is included in the 75K or higher inverter. The option cannot be purchased separately. More Details >>

    • No:21252
    • Release Date:2018/08/22 16:26
  • Replacement

    The station number and baud rate were set using the dial for the FR-A5NC, but parameter is used for the FR-A7NC. Pr.542 (Communication station number (CC-Lin... More Details >>

    • No:21248
    • Release Date:2018/08/22 16:26
  • Replacement

    It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>