FAQ within [ FREQROL-A700 ]

241-250 of Total 351

prev 25 / 36page next
  • Frequency setting

    Change the value of Pr.18 (High speed maximum frequency).You can set any frequency within the range defined by Pr.18. More Details >>

    • No:21737
    • Release Date:2018/08/22 16:29
  • Terminal setting

    To use the terminal as voltage input, you need to:- Set Pr.267 (Terminal 4 input selection).- Set the voltage/current input switch on the inverter board.- Se... More Details >>

    • No:21771
    • Release Date:2018/08/22 16:29
  • Frequency setting

    To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>

    • No:21799
    • Release Date:2018/08/22 16:29
  • Terminal FM

    Set Pr.56 (Current monitor reference) to "10A". More Details >>

    • No:21865
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>

    • No:21915
    • Release Date:2018/08/22 16:30
  • 4 to 20 mA output

    Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>

    • No:21246
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Calibrate C6 (Pr.904) (Terminal 4 frequency setting bias frequency) and C7 (Pr.905) (Terminal 4 frequency setting gain frequency). If the situation does not ... More Details >>

    • No:21265
    • Release Date:2018/08/22 16:26
  • Brake unit

    The resistors cannot be used in combination other than described. Operations of brake units and inverters are not verified. When resistors are used in uncert... More Details >>

    • No:21328
    • Release Date:2018/08/22 16:27
  • Parameter

    Press the "MODE" key on the operation panel several times to display "P.0" and parameter setting screen. Then turn the setting dial to display "C..." screen ... More Details >>

    • No:21336
    • Release Date:2018/08/22 16:27
  • Frequency setting

    Normally, any of the PU, EXT, or NET LED turns ON.Check if the parameter unit FR-PU04/FR-PU07 or operation panel FR-PA07 is externally connected to the PU co... More Details >>

    • No:21803
    • Release Date:2018/08/22 16:29