The value of Pr.20 (Acceleration/deceleration standard frequency) is corresponding to 1 s. (Initial value: 60 Hz) More Details >>
- No:21185
- Release Date:2018/08/22 16:26
-
The total wiring length is as follows: 100 m + (20 m × 5) = 200m. More Details >>
- No:21144
- Release Date:2018/08/22 16:26
-
If you are using CC-Link just to monitor the inverter and using the analog signal and multi-speed setting to set the frequency, you need to input them extern... More Details >>
- No:21900
- Release Date:2018/08/22 16:29
-
1. Set Pr.162 to "10" (Frequency search at every start).2. You can ignore the setting if the motor excitation current is unknown. More Details >>
- No:21718
- Release Date:2018/08/22 16:29
-
The FR-A5AY cannot be used in the FR-A700 (F700(P)). It cannot be installed due to the difference of the connector shape. More Details >>
- No:21260
- Release Date:2018/08/22 16:26
-
After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>
- No:21256
- Release Date:2018/08/22 16:26
-
You can start/stop operation, set the frequency, read/write parameters, and monitor the inverter via CC-Link communication. More Details >>
- No:21901
- Release Date:2018/08/22 16:29
-
Set Pr.79 (Operation mode) setting value to "0", "2", or "6", Pr.340 (Communication startup mode selection) other than the setting value, Pr.542 (Station num... More Details >>
- No:21896
- Release Date:2018/08/22 16:29
-
Check if the CC-Link wires are short-circuited and/or station numbers are duplicated. More Details >>
- No:21891
- Release Date:2018/08/22 16:29
-
Up to 42 units can be connected. (When only inverters are connected) More Details >>
- No:21873
- Release Date:2018/08/22 16:29