The output voltage will not be imbalanced when the inverter is used. (Since AC is converted into DC and then into AC, the output voltage is hardly effected f... More Details >>
The 75K or higher DC reactor is included in the 75K or higher inverter. The option cannot be purchased separately. More Details >>
Set Pr.52 (PU/DU main display data selection) to "5".Set the monitor as the third monitor, frequency -> current -> setting frequency. More Details >>
Set Pr.270 (Stop-on-contact control) to "1".Set Pr.184 (RES terminal function selection) to "3" to choose the RT signal function.When the terminals RL and RT... More Details >>
When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>
Blinking of the "RUN" LED on the panel suggests that the frequency command may not be input. Create a frequency setting data as for the forward rotation comm... More Details >>
NET mode, external operation switching
You can switch between the NET mode and external operation.Assign the X66 signal (Operation switching) to an unused terminal for switching.Also, set Pr.79 (O... More Details >>
Set Pr.56 (Current monitor reference) to "10A". More Details >>
Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency). More Details >>
No. You cannot check the accumulated number of rotations on the monitor. More Details >>