Check the setting value of Pr.37 (Speed display). When the machine speed is set, Pr.811 is disabled. Change the setting to the rotation speed. More Details >>
- No:21161
- Release Date:2018/08/22 16:26
-
Turn OFF the BOF signal when switching the operation from forward rotation to reverse rotation. More Details >>
- No:21184
- Release Date:2018/08/22 16:26
-
The brake unit operates when the bus voltage exceeds the brake operation voltage. More Details >>
- No:21272
- Release Date:2018/08/22 16:26
-
Since the Advanced magnetic flux vector control method uses slip compensation to compensate the frequency, the value is not shown as exactly 60 Hz.For V/F co... More Details >>
- No:21807
- Release Date:2018/08/22 16:29
-
Advanced magnetic flux vector control
Yes. Set Pr.89 (Speed control gain) to "0". More Details >>
- No:21690
- Release Date:2018/08/22 16:28
-
Check the parameters listed below necessary for tuning again.Pr.9, Pr.71, Pr.80, Pr.81, Pr.83, Pr.84, and Pr.96 More Details >>
- No:21726
- Release Date:2018/08/22 16:29
-
Output frequency monitor value
When running the inverter after auto tuning, the frequency setting value is increased by the amount of the motor slippage, resulting in a higher monitor valu... More Details >>
- No:21781
- Release Date:2018/08/22 16:29
-
Set Pr.9, Pr.71, Pr.80, Pr.81, Pr.83, Pr.84, and Pr.96. More Details >>
- No:21721
- Release Date:2018/08/22 16:29
-
Set it to "13" (Constant-torque). More Details >>
- No:21752
- Release Date:2018/08/22 16:29
-
When running the inverter in Advanced magnetic flux vector control, the frequency setting value is increased by the amount of the motor's slippage, resulting... More Details >>
- No:21801
- Release Date:2018/08/22 16:29