  • Output frequency

    When Pr.80 and Pr.81 are set to the value other than "9999", control other than V/F control is performed. For the FR-F700(P) FR-D700, and FR-F700PJ, Pr.81 is... More Details >>

    • No:21259
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Multi-speed setting

    Priorities are: Low speed (RL) > Middle speed (RM) > High speed (RH).For example, if the low speed (RL) and middle speed (RM) signals are input simulta... More Details >>

    • No:21772
    • Release Date:2018/08/22 16:29
  • Frequency meter and calibration resistor

    Frequency meter: YM206NRI 1 mA Calibration resistor: RV24YN 10 k?. More Details >>

    • No:21357
    • Release Date:2018/08/22 16:27
  • Frequency setting

    The output frequency is not changed by the maximum frequency setting. It can be changed by the following methods. - Set the frequency on the operation panel.... More Details >>

    • No:21347
    • Release Date:2018/08/22 16:27
  • Input phase loss

    The detection time 1 s cannot be changed. More Details >>

    • No:21277
    • Release Date:2018/08/22 16:26
  • Frequency manual controller FR-AX

    Considering voltage drop of the internal power supply and influence by noise, the wiring length should be 30 m or less. More Details >>

    • No:21809
    • Release Date:2018/08/22 16:29
  • Faults history

    Press the "MODE" key on the operation panel several times to display the faults history screen "E---". Then turn the setting dial to display the error displa... More Details >>

    • No:21355
    • Release Date:2018/08/22 16:27
  • Terminals P1 and P

    Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>

    • No:21921
    • Release Date:2018/08/22 16:30
  • FR-RC

    Pr.30 = "1" and Pr.70 = "0". More Details >>

    • No:21143
    • Release Date:2018/08/22 16:26