FAQ within [ FREQROL-A700 ]
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26
-
Yes.You can issue operation (forward/reverse), frequency setting, parameter read/write, and operation monitor commands. More Details >>
- No:21899
- Release Date:2018/08/22 16:29
-
CC-Link station number setting
Change the setting in the PU operation mode. More Details >>
- No:21747
- Release Date:2018/08/22 16:29
-
Yes. More Details >>
- No:21871
- Release Date:2018/08/22 16:29
-
If you are using CC-Link just to monitor the inverter and using the analog signal and multi-speed setting to set the frequency, you need to input them extern... More Details >>
- No:21900
- Release Date:2018/08/22 16:29
-
Yes. The FR-A7NC E kit contains a dedicated front cover since its size changes by the installed board.You can additionally purchase the FR-A7NC E kit cover o... More Details >>
- No:21889
- Release Date:2018/08/22 16:29
-
No, it is not available. It is only available in the External operation mode or combined operation mode (PU speed command and External operation command (Pr.... More Details >>
- No:21192
- Release Date:2018/08/22 16:26
-
The value of Pr.20 (Acceleration/deceleration standard frequency) is corresponding to 1 s. (Initial value: 60 Hz) More Details >>
- No:21185
- Release Date:2018/08/22 16:26
-
They are not output while the motor is coasting even under Vector control. More Details >>
- No:21158
- Release Date:2018/08/22 16:26
-
Advanced magnetic flux vector control
To use Advanced magnetic flux vector control, basically set Pr.9, Pr.80, Pr.81, Pr.71, and Pr.800.Auto tuning is necessary in some cases. Set Pr.83, Pr.84, a... More Details >>