  • Rotation speed display

    It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>

    • No:21180
    • Release Date:2018/08/22 16:26
  • 400 V inverter

    No, it does not run. "Err" is displayed when it is operated. Always input the same voltage (400 V) to the main power supply and control power supply. More Details >>

    • No:21179
    • Release Date:2018/08/22 16:26
  • Auto tuning

    Set "33" or "34". More Details >>

    • No:21167
    • Release Date:2018/08/22 16:26
  • Setting resolution switching

    Check the setting value of Pr.37 (Speed display). When the machine speed is set, Pr.811 is disabled. Change the setting to the rotation speed. More Details >>

    • No:21161
    • Release Date:2018/08/22 16:26
  • Vector control

    Install the resistor between the terminals PC and OH. More Details >>

    • No:21160
    • Release Date:2018/08/22 16:26
  • Vector control

    They are not output while the motor is coasting even under Vector control. More Details >>

    • No:21158
    • Release Date:2018/08/22 16:26
  • Wiring length

    Under Real sensorless vector control, the maximum wiring length is 500 m. Under Vector control with encoder, the maximum wiring length is 100 m. More Details >>

    • No:21133
    • Release Date:2018/08/22 16:26
  • FR-A800

    - The 280K or lower has the installation size compatibility. - The 315K or higher does not have the installation compatibility; because the inverter unit and... More Details >>

    • No:21109
    • Release Date:2018/08/22 16:25
  • FR-A800

    No. Check the parameter setting of the A700, and then adjust the parameter setting of the A800 to those of the A700. For the details, refer to the replacemen... More Details >>

    • No:21107
    • Release Date:2018/08/22 16:25
  • FR-A701

    The AC reactor (FR-HAL) is built in the FR-A701. (The circuit type in the Harmonic Suppression Guidelines is three-phase bridge (capacitor smoothed), with re... More Details >>

    • No:21011
    • Release Date:2018/08/22 16:25