Normally, the inverter starts up in the NET operation mode at power ON when Pr.340 is set to "10" and Pr.79 is set to "0". When it starts up in the PU operat... More Details >>
- No:21319
- Release Date:2018/08/22 16:27
-
Since the operation panels of the E700, D700, and F700PJ do not have keys for the forward (FWD) and reverse (REV) rotations, you can only command rotation in... More Details >>
- No:21841
- Release Date:2018/08/22 16:29
-
Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>
- No:21780
- Release Date:2018/08/22 16:29
-
When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>
- No:21327
- Release Date:2018/08/22 16:27
-
When Pr.80 and Pr.81 are set to the value other than "9999", control other than V/F control is performed. For the FR-F700(P) FR-D700, and FR-F700PJ, Pr.81 is... More Details >>
- No:21259
- Release Date:2018/08/22 16:26
-
Switching between PU and NET operations
Even after setting Pr.340 to "10", the change is reflected after resetting the power supply.Perform the power reset.Since changes to the communication parame... More Details >>
- No:21696
- Release Date:2018/08/22 16:28
-
Use the inverter's calibration parameters Pr.C2/C3, Pr.125/C4 to adjust the bias and gain for each inverter.Connect the wires from the frequency setting pote... More Details >>
- No:21728
- Release Date:2018/08/22 16:29
-
The FR Configurator FR-SW3-SETUP-WJ can only allow for test operation.Since this is a tool to support the system launch and maintenance, it is not designed f... More Details >>
- No:21914
- Release Date:2018/08/22 16:30
-
Set Pr.79 to "2" (external operation mode). More Details >>
- No:21818
- Release Date:2018/08/22 16:29
-
When Pr.79 is set to "3", the JOG operation is not available by turning ON the terminal JOG.Instead of the JOG function, you can set the low-speed RL of the ... More Details >>
- No:21760
- Release Date:2018/08/22 16:29
31-40 of Total 351