No, it does not run. "Err" is displayed when it is operated. Always input the same voltage (400 V) to the main power supply and control power supply. More Details >>
- No:21179
- Release Date:2018/08/22 16:26
-
If you have already set other parameters necessary for tuning (Pr.9, Pr.71, Pr.80, Pr.81, Pr.83, and Pr.84), press the MODE button to return to the frequency... More Details >>
- No:21750
- Release Date:2018/08/22 16:29
-
If "1" is not shown on the frequency monitor, some of the parameters necessary for auto tuning may not be set correctly.Set rated motor current of Pr.81 (Num... More Details >>
- No:21751
- Release Date:2018/08/22 16:29
-
When running the inverter in Advanced magnetic flux vector control, the frequency setting value is increased by the amount of the motor's slippage, resulting... More Details >>
- No:21801
- Release Date:2018/08/22 16:29
-
Set it to "13" (Constant-torque). More Details >>
- No:21752
- Release Date:2018/08/22 16:29
-
You can select from the output power (in 0.01 kW units) and cumulative energy (in 1 kWh/0.01 kWh units). More Details >>
- No:21885
- Release Date:2018/08/22 16:29
-
The 75K or higher DC reactor is included in the 75K or higher inverter. The option cannot be purchased separately. More Details >>
- No:21252
- Release Date:2018/08/22 16:26
-
Advanced magnetic flux vector control
Yes. Set Pr.89 (Speed control gain) to "0". More Details >>
- No:21690
- Release Date:2018/08/22 16:28
-
Check if any device is connected to the inverter's external terminal.In particular, check if MRS and SD are short-circuited.If they are short-circuited, open... More Details >>
- No:21753
- Release Date:2018/08/22 16:29
-
Keep Y100D turned ON if you are changing the frequency continuously. More Details >>
- No:21883
- Release Date:2018/08/22 16:29