  • RUN blinks

    When using the setting dial to set the frequency, turn the dial and press the "SET" key while the desired value flickers. (The value and "F" flicker alternat... More Details >>

    • No:21692
    • Release Date:2018/08/22 16:28
  • Switching between PU and NET operations

    Even after setting Pr.340 to "10", the change is reflected after resetting the power supply.Perform the power reset.Since changes to the communication parame... More Details >>

    • No:21696
    • Release Date:2018/08/22 16:28
  • Printing files saved in the previous version of FR-Configurator

    The parameter file of FR-SW3 cannot be printed using FR-SW2. The latest version of FR-SW3 can be downloaded from the Mitsubishi Electric FA Global Website. U... More Details >>

    • No:21315
    • Release Date:2018/08/22 16:27
  • RS-485 communication

    Blinking of the "RUN" LED on the panel suggests that the frequency command may not be input. Create a frequency setting data as for the forward rotation comm... More Details >>

    • No:21301
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Set C5 (Pr.904) (Terminal 4 frequency setting bias frequency) to 0 Hz and Pr.126 (Terminal 4 frequency setting gain frequency) to 50 Hz. More Details >>

    • No:21268
    • Release Date:2018/08/22 16:26
  • Operation panel

    This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>

    • No:21775
    • Release Date:2018/08/22 16:29
  • Electronic thermal O/L relay setting

    When using multiple motors, connect an external thermal for each of them. Set Pr.9 to "0" to disable the function. (When multiple motors are present, it is n... More Details >>

    • No:21676
    • Release Date:2018/08/22 16:28
  • UL standard

    Both 200 V class and 400 V class are suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 264 V maximum (528 V f... More Details >>

    • No:21358
    • Release Date:2018/08/22 16:27
  • Electromagnetic contactor

    It is not recommended to start and stop the inverter with the electromagnetic contactor (MC). This will accelerate the deterioration (due to the inrush curre... More Details >>

    • No:21322
    • Release Date:2018/08/22 16:27
  • Frequency setting

    When the frequency is set using the setting dial, it is not necessary to set it again.The inverter memorizes the setting value internally even after the powe... More Details >>

    • No:21842
    • Release Date:2018/08/22 16:29