  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Change the value of Pr.18 (High speed maximum frequency).You can set any frequency within the range defined by Pr.18. More Details >>

    • No:21737
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>

    • No:21743
    • Release Date:2018/08/22 16:29
  • Auto tuning

    When offline auto tuning ends normally, the setting of this parameter changes to "3".This means that auto tuning completed normally.If the setting value is "... More Details >>

    • No:21748
    • Release Date:2018/08/22 16:29
  • Auto tuning

    Yes. More Details >>

    • No:21749
    • Release Date:2018/08/22 16:29
  • Auto tuning

    Set it to "13" (Constant-torque).   More Details >>

    • No:21752
    • Release Date:2018/08/22 16:29
  • Auto tuning

    Check if any device is connected to the inverter's external terminal.In particular, check if MRS and SD are short-circuited.If they are short-circuited, open... More Details >>

    • No:21753
    • Release Date:2018/08/22 16:29
  • Advanced magnetic flux vector control

    Check the parameters necessary for tuning again.Check if Pr.9 (Electronic thermal O/L relay) and Pr.81 (Number of motor poles) are set correctly. More Details >>

    • No:21754
    • Release Date:2018/08/22 16:29
  • Advanced magnetic flux vector control

    When using the geared motor GM-S(B), set Pr.71 to "13" and also set Pr.9, Pr.80, and Pr.81.Perform auto tuning as required. Perform auto tuning as required. ... More Details >>

    • No:21756
    • Release Date:2018/08/22 16:29