FAQ within [ FREQROL-A700 ]

61-70 of Total 352

prev 7 / 36page next
  • CC-Link

    Input 4 words, output 4 words for version 1. 2, 4, and 8 times for version 2. More Details >>

    • No:21874
    • Release Date:2018/08/22 16:29
  • CC-Link

    Create a ladder program to read inverter faults on the programmable controller.Set the instruction code (H74-H77) and turn ON the instruction code execution ... More Details >>

    • No:21886
    • Release Date:2018/08/22 16:29
  • CC-Link

    No problem. The inverter actually occupies the reserved bits and does not use them. More Details >>

    • No:21890
    • Release Date:2018/08/22 16:29
  • CC-Link

    Set Pr.340 (Communication startup mode selection) to other than "0".Also, set Pr.79 (Operation mode) to "0", "2", or "6".Powering the inverter on automatical... More Details >>

    • No:21903
    • Release Date:2018/08/22 16:30
  • CC-Link

    You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>

    • No:21905
    • Release Date:2018/08/22 16:30
  • Fast-response current limit

    It is not activated because the function itself is disabled. More Details >>

    • No:21137
    • Release Date:2018/08/22 16:26
  • Electronic bypass function

    The operation cannot be manually switched to the commercial power supply operation at an inverter fault. The operation can be automatically switched to the c... More Details >>

    • No:21191
    • Release Date:2018/08/22 16:26
  • Changing the control method

    Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>

    • No:21245
    • Release Date:2018/08/22 16:26
  • Brake resistor

    It will be the shared type. More Details >>

    • No:21331
    • Release Date:2018/08/22 16:27
  • Offline auto tuning

    When auto tuning completes normally, the setting value of Pr.96 (Auto tuning setting/status) is changed to "3". When it is not changed, check the set paramet... More Details >>

    • No:21353
    • Release Date:2018/08/22 16:27