  • Parameter

    No parameter can be used to directly set this time.Changing Pr.9 (Electronic thermal O/L relay) changes the time. More Details >>

    • No:21769
    • Release Date:2018/08/22 16:29
  • Switching between external operation and NET operation

    You can switch between external operation and NET operation by turning ON/OFF the terminal X66 (RM). You can switch while Pr.79 (Operation mode) is set to "6... More Details >>

    • No:21688
    • Release Date:2018/08/22 16:28
  • Brake unit

    The resistors cannot be used in combination other than described. Operations of brake units and inverters are not verified. When resistors are used in uncert... More Details >>

    • No:21328
    • Release Date:2018/08/22 16:27
  • Supported model for FR-Configurator

    The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>

    • No:21314
    • Release Date:2018/08/22 16:26
  • Using external potentiometer and multi-speed operation together

    You can use an external potentiometer and multi-speed operation together.When an external potentiometer signal input and multi-speed setting occur simultaneo... More Details >>

    • No:21920
    • Release Date:2018/08/22 16:30
  • CC-Link

    1. You can reset the inverter from an external terminal.You can do it without regard to the setting of Pr.338 (Communication operation command source) and Pr... More Details >>

    • No:21837
    • Release Date:2018/08/22 16:29
  • Electromagnetic contactor

    It is not recommended to start and stop the inverter with the electromagnetic contactor (MC). This will accelerate the deterioration (due to the inrush curre... More Details >>

    • No:21322
    • Release Date:2018/08/22 16:27
  • Life diagnosis

    When Pr.259 (Main circuit capacitor life measuring) is set to "1", the life diagnosis is ready. Turning OFF the power supply starts measuring the life of the... More Details >>

    • No:21283
    • Release Date:2018/08/22 16:26
  • Frequency setting

    The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>

    • No:21800
    • Release Date:2018/08/22 16:29
  • Setting frequency

    Set Pr.52 (DU/PU main display data selection) to "5".This allows for displaying the setting frequency on the voltage monitor.Then, switch to the monitor mode... More Details >>

    • No:21784
    • Release Date:2018/08/22 16:29