101-110 of Total 295

prev 11 / 30page next
  • Language in FR Configurator

    FR-Configurator (FR-SW3-STUP-WJ) is the Japanese version. FR-Configurator (FR-SW3-SETUP-WE) is the English version. More Details >>

    • No:21308
    • Release Date:2018/08/22 16:26
  • Capacity selection

    Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>

    • No:21326
    • Release Date:2018/08/22 16:27
  • Megger test

    When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>

    • No:21327
    • Release Date:2018/08/22 16:27
  • Wiring the terminal

    There is no problem with the wiring. Keep the rating (24 VDC, 0.1 A) of the terminal PC. More Details >>

    • No:21342
    • Release Date:2018/08/22 16:27
  • PU operation

    1. Yes. 2. Set Pr.17 to "2".  3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>

    • No:21359
    • Release Date:2018/08/22 16:27
  • Frequency setting

    Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency).   More Details >>

    • No:21744
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Yes.The inverter requires the start signal and frequency setting signal. More Details >>

    • No:21793
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) instead of Pr.1 (Maximum frequency).   More Details >>

    • No:21802
    • Release Date:2018/08/22 16:29
  • Frequency meter

    First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>

    • No:21808
    • Release Date:2018/08/22 16:29
  • Frequency manual controller FR-AX

    Considering voltage drop of the internal power supply and influence by noise, the wiring length should be 30 m or less. More Details >>

    • No:21809
    • Release Date:2018/08/22 16:29

101-110 of Total 295