FAQ within [ FREQROL-F700 ]

121-130 of Total 296

prev 13 / 30page next
  • FR-A7AR E kit (Relay output function)

    Yes, you can set all of the three relay contacts to fault contacts.Set Pr.320 (RA1 output selection), 321 (RA2 output selection), and 322 (RA3 output selecti... More Details >>

    • No:21712
    • Release Date:2018/08/22 16:29
  • Monitor indicator

    No. You cannot check the accumulated number of rotations on the monitor.   More Details >>

    • No:21715
    • Release Date:2018/08/22 16:29
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • CC-Link

    To set the frequency via CC-Link communication, the NET mode should be selected. The new parameter setting is applied after powering OFF and then ON the inve... More Details >>

    • No:21763
    • Release Date:2018/08/22 16:29
  • Program command

    This subroutine is to check the data link status and needs to be executed only once at the start of the program. More Details >>

    • No:21767
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>

    • No:21768
    • Release Date:2018/08/22 16:29
  • Output current value

    The detection level of the output current value cannot be changed using a potentiometer or a similar device.   More Details >>

    • No:21779
    • Release Date:2018/08/22 16:29
  • Setting frequency

    Set Pr.52 (DU/PU main display data selection) to "5".This allows for displaying the setting frequency on the voltage monitor.Then, switch to the monitor mode... More Details >>

    • No:21784
    • Release Date:2018/08/22 16:29
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Yes.The inverter requires the start signal and frequency setting signal. More Details >>

    • No:21793
    • Release Date:2018/08/22 16:29

121-130 of Total 296