FAQ within [ FREQROL-F700 ]

131-140 of Total 295

prev 14 / 30page next
  • CC-Link

    Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>

    • No:21833
    • Release Date:2018/08/22 16:29
  • CC-Link

    The start commands cannot be input from both sources simultaneously because the operation command source is specified.You can switch the command source as ne... More Details >>

    • No:21828
    • Release Date:2018/08/22 16:29
  • CC-Link

    Yes. Set the first monitor code in the lower 8 bits and the second monitor code in the upper 8 bits of RWwn.Set H6F to the first monitor code, and H70 to the... More Details >>

    • No:21824
    • Release Date:2018/08/22 16:29
  • Running frequency

    Check the setting of Pr.1 (Maximum frequency) and Pr.18 (High speed maximum frequency).Pr.1 is initially set to "120 Hz". More Details >>

    • No:21821
    • Release Date:2018/08/22 16:29
  • External multi-speed setting and multi-speed command

    It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>

    • No:21815
    • Release Date:2018/08/22 16:29
  • Programmable controller

    The error LED on the master side of the programmable controller blinks (faulty station present).According to the SW80 station information, an error flag is a... More Details >>

    • No:21813
    • Release Date:2018/08/22 16:29
  • Magnetic flux vector control

    For low-speed operation, perform auto tuning and use (Advanced) magnetic flux vector control. More Details >>

    • No:21810
    • Release Date:2018/08/22 16:29
  • Frequency setting

    The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>

    • No:21800
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can change the terminal 4 to voltage input. (The terminal 4 is set to the current input terminal at the initial setting.)To change the terminal 4 to volt... More Details >>

    • No:21787
    • Release Date:2018/08/22 16:29
  • Operation panel

    This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>

    • No:21775
    • Release Date:2018/08/22 16:29