FAQ within [ FREQROL-F700 ]

171-180 of Total 295

prev 18 / 30page next
  • Rated frequency setting

    Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>

    • No:21280
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Up to 30 m. (To avoid noise and voltage drop)   More Details >>

    • No:21910
    • Release Date:2018/08/22 16:30
  • CC-Link

    You can use optional items, such as enclosure surface operation panel FR-PA07 and parameter unit FR-PU07.Use the PU connector of the inverter for connection.... More Details >>

    • No:21832
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency).   More Details >>

    • No:21744
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Even while the inverter is operating, you can use the setting dial to change the frequency and then press the SET key and the inverter operates at the new fr... More Details >>

    • No:21739
    • Release Date:2018/08/22 16:29
  • Operation method

    Set Pr.79 (Operation mode) to "3" and Pr.161 (Frequency setting/key lock operation selection) to "1". More Details >>

    • No:21249
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Set Pr.13 (Starting frequency) or Pr.2 (Lower limit) to "5 Hz".Also set Pr.10 (DC injection brake operation frequency) to "5 Hz".The inverter does not operat... More Details >>

    • No:21790
    • Release Date:2018/08/22 16:29
  • Support of Chinese

    Some types are designed for the Chinese market and provide Chinese manuals. (Note that the specifications of these types are partially different from the spe... More Details >>

    • No:21479
    • Release Date:2018/08/22 16:27
  • Brake resistor

    Use two resistors for the high-duty brake resistor FR-ABR-15K. (Connect two resistors of 18 ? in parallel.) More Details >>

    • No:21329
    • Release Date:2018/08/22 16:27
  • Parameter setting

    Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>

    • No:21270
    • Release Date:2018/08/22 16:26