Increasing the value of Pr.0 (Torque boost) increases the output voltage, and the output current also increases.Note that increasing this value too high puts... More Details >>
- No:21732
- Release Date:2018/08/22 16:29
-
You can set the running frequency up to 400 Hz.It depends on the specifications of the motor used whether or not operation with a frequency of 120 Hz or high... More Details >>
- No:21738
- Release Date:2018/08/22 16:29
-
This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>
- No:21743
- Release Date:2018/08/22 16:29
-
After setting Pr.340 to "10", you need to power OFF then ON the inverter to make the new setting enabled because you are setting the operation upon power-on.... More Details >>
- No:21759
- Release Date:2018/08/22 16:29
-
This subroutine is to check the data link status and needs to be executed only once at the start of the program. More Details >>
- No:21767
- Release Date:2018/08/22 16:29
-
This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>
- No:21775
- Release Date:2018/08/22 16:29
-
Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>
- No:21780
- Release Date:2018/08/22 16:29
-
Set Pr.3 (Base frequency) and Pr.18 (High speed maximum frequency) to "340 Hz", Pr.19 (Base frequency voltage) to "200 V", Pr.125 (Terminal 2 frequency setti... More Details >>
- No:21789
- Release Date:2018/08/22 16:29
-
As the AS-OX has the "0ADJ" potentiometer for frequency meter calibration, use it to adjust the meter so that both readings match. More Details >>
- No:21795
- Release Date:2018/08/22 16:29
-
Check the setting of Pr.79 (Operation mode).If the setting value is "2", frequency commands from an external terminal is effective and the frequency setting ... More Details >>
- No:21797
- Release Date:2018/08/22 16:29