  • Adjustment of analog gain

    Use Pr.903 (Frequency setting voltage gain) for setting the FR-E500. For the 700 series, use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (... More Details >>

    • No:21689
    • Release Date:2018/08/22 16:28
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • Terminal FM

    No. This is because the current cannot flow if the total internal impedance of the meter connected to the terminal FM is 300 Ω or higher.You can connect mult... More Details >>

    • No:21864
    • Release Date:2018/08/22 16:29
  • Switching between External operation mode and PU operation mode

    Assign X16 signal, and set Pr.79 to "0", to switch the operation mode with turning ON/OFF X16 signal. More Details >>

    • No:21288
    • Release Date:2018/08/22 16:26
  • Frequency setting

    When turning the setting dial to set the frequency, press the "SET" key while the desired value blinks. (The setting frequency and "F" flicker alternately.) More Details >>

    • No:21742
    • Release Date:2018/08/22 16:29
  • Terminal FM

    You can connect a 1 mA full scale ammeter with internal resistance 300 Ω or lower. More Details >>

    • No:21680
    • Release Date:2018/08/22 16:28
  • Frequency setting

    Set Pr.13 (Starting frequency) or Pr.2 (Lower limit) to "5 Hz".Also set Pr.10 (DC injection brake operation frequency) to "5 Hz".The inverter does not operat... More Details >>

    • No:21790
    • Release Date:2018/08/22 16:29
  • Frequency setting

    No. Use a frequency setting potentiometer with the resistance of 1 kΩ and B characteristics.Input voltage is not linear due to the inverter's internal impeda... More Details >>

    • No:21911
    • Release Date:2018/08/22 16:30
  • FR-PU04

    While the FR-PU04 does not display parameter names, it displays parameter numbers and you can set them. More Details >>

    • No:21919
    • Release Date:2018/08/22 16:30
  • Cooling fan

    Pr.244 (Cooling fan operation selection) controls turning ON/OFF of the cooling fan and is initially set to "1". When the inverter is powered ON, the cooling... More Details >>

    • No:21670