  • UL standard

    Both 200 V class and 400 V class are suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 264 V maximum (528 V f... More Details >>

    • No:21358
    • Release Date:2018/08/22 16:27
  • FR-PA07

    When Pr.79 is set to "3", since the start command is in the External operation mode, the RUN key of FR-PA07 does not work. More Details >>

    • No:21303
    • Release Date:2018/08/22 16:26
  • Parameter read

    By setting Pr.160 (User group read selection ("Extended function display selection" for D700)) to "0", all the parameters can be read. More Details >>

    • No:21262
    • Release Date:2018/08/22 16:26
  • Changing the control method

    Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>

    • No:21245
    • Release Date:2018/08/22 16:26
  • Running frequency setting

    Pr.338 is for the communication operation command source at communication operation and specifies the command source to supply the start signal.Pr.339 is for... More Details >>

    • No:21880
    • Release Date:2018/08/22 16:29
  • Model setting in FR-Configurator

    Check the version of FR-Configurator (FR-SW3-SETUP-WJ). If the version is "1.00", it does not support or detect the FR-E740. Version "2.00" supports the FR-E... More Details >>

    • No:21309
    • Release Date:2018/08/22 16:26
  • External installationRated current

    Since the external thermal prevents the motor from being overheated, install it between the output terminal of the inverter and the motor.The rated current i... More Details >>

    • No:21817
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Yes.The inverter requires the start signal and frequency setting signal. More Details >>

    • No:21793
    • Release Date:2018/08/22 16:29
  • Frequency setting

    It is not stored in a parameter but memorized as the frequency setting value after acceleration by the acceleration signal.You can also choose whether or not... More Details >>

    • No:21733
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Even though the maximum frequency setting is changed using CC-Link, the running frequency is not changed. By writing the set frequency to the remote register... More Details >>

    • No:21346
    • Release Date:2018/08/22 16:27