Normally, the inverter starts up in the NET operation mode at power ON when Pr.340 is set to "10" and Pr.79 is set to "0". When it starts up in the PU operat... More Details >>
- No:21319
- Release Date:2018/08/22 16:27
-
When the pulse is counted and displayed, 1440 pulses are output with the frequency of the inverter is 60 Hz. Since these pulses are limited to 2400 pulses, a... More Details >>
- No:21334
- Release Date:2018/08/22 16:27
-
Yes, you can set Pr.20 to 20 Hz. More Details >>
- No:21683
- Release Date:2018/08/22 16:28
-
Switching between external operation and NET operation
You can write frequency setting by setting Pr.339 (Communication speed command source) to "0". More Details >>
- No:21687
- Release Date:2018/08/22 16:28
-
10 VDC voltage from terminal 10
Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>
- No:21727
- Release Date:2018/08/22 16:29
-
No. You cannot change the setting during operation.However, setting Pr.77 (Parameter write selection) to "2" allows for the setting change during operation. ... More Details >>
- No:21734
- Release Date:2018/08/22 16:29
-
Set Pr.52 (DU/PU main display data selection) to "100".Displaying the setting frequency while the inverter is stopped and the output frequency while it is op... More Details >>
- No:21783
- Release Date:2018/08/22 16:29
-
Pr.1 (Maximum frequency) or Pr.18 (High speed maximum frequency). More Details >>
- No:21805
- Release Date:2018/08/22 16:29
-
Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>
- No:21845
- Release Date:2018/08/22 16:29
-
Check that the wiring of the terminal 4 and 5 are not reversed. More Details >>
- No:21266
- Release Date:2018/08/22 16:26