The calibration parameter C6 (Terminal 4 frequency setting bias) is initially set to "20%". Therefore, voltage input to the terminal 4 does not become effect... More Details >>
- No:21806
- Release Date:2018/08/22 16:29
-
In this case, the JOG operation is prioritized.When the terminals JOG and SD are short-circuited and turned ON, the frequency setting by the external potenti... More Details >>
- No:21804
- Release Date:2018/08/22 16:29
-
Increasing the value of Pr.0 (Torque boost) increases the output voltage, and the output current also increases.Note that increasing this value too high puts... More Details >>
- No:21732
- Release Date:2018/08/22 16:29
-
For the set frequency 60 Hz, ±6 Hz is applied and thus the up to frequency signal is output between 54 Hz and 66 Hz. During acceleration/deceleration to the ... More Details >>
- No:21348
- Release Date:2018/08/22 16:27
-
Set Pr.55 (Frequency monitoring reference) of the first inverter to 70 Hz. More Details >>
- No:21257
- Release Date:2018/08/22 16:26
-
Turn ON and OFF the RES signal to enable the inverter-driven operation. More Details >>
- No:21190
- Release Date:2018/08/22 16:26
-
The signals MRS and CS are required when the automatic bypass sequence enabled. More Details >>
- No:21187
- Release Date:2018/08/22 16:26
-
Yes.You can issue operation (forward/reverse), frequency setting, parameter read/write, and operation monitor commands. More Details >>
- No:21899
- Release Date:2018/08/22 16:29
-
Connect the wire to the optional FR-A7NC's terminal block. (The terminal block is detachable.) More Details >>
- No:21875
- Release Date:2018/08/22 16:29
-
Set Pr.56 (Current monitor reference) to "10A". More Details >>
- No:21865
- Release Date:2018/08/22 16:29