    Set Pr.340 (Communication startup mode selection) to other than "0".Also, set Pr.79 (Operation mode) to "0", "2", or "6".Powering the inverter on automatical... More Details >>

    • No:21903
    • Release Date:2018/08/22 16:30
  • Connection cable of FR-Configurator

    It is the standardized Mini-B connector. More Details >>

    • No:21312
    • Release Date:2018/08/22 16:26
  • Running frequency

    Check the setting of Pr.1 (Maximum frequency) and Pr.18 (High speed maximum frequency).Pr.1 is initially set to "120 Hz". More Details >>

    • No:21821
    • Release Date:2018/08/22 16:29
  • Frequency setting

    From the LED, it is considered that the operation mode Pr.79 is set to "3".The PU and EXT LEDs turn ON with this setting.In this state, you cannot change bet... More Details >>

    • No:21741
    • Release Date:2018/08/22 16:29
  • Frequency setting signal

    Check the AU signal (AU - SD). To use the terminal 4, the AU signal (AU - SD) needs to be turned ON. Turning ON the AU signal (AU - SD) disables the terminal 2. More Details >>

    • No:21267
    • Release Date:2018/08/22 16:26
  • Monitor indicator

    The first priority window of the monitor may be set to the current.When the current is displayed on the monitor (the unit is "A"), press "SET" to switch to t... More Details >>

    • No:21765
    • Release Date:2018/08/22 16:29
  • Operation mode setting value

    Set Pr.79 to "2" (external operation mode).    More Details >>

    • No:21818
    • Release Date:2018/08/22 16:29
  • Proportional band of multiple inverters

    By importing the operation frequency from the AM terminal (analog output) of the first inverter to the FR-FH (ratio setter), the operation command which is p... More Details >>

    • No:21250
    • Release Date:2018/08/22 16:26
  • NET operation mode

    Normally, the inverter starts up in the NET operation mode at power ON when Pr.340 is set to "10" and Pr.79 is set to "0". When it starts up in the PU operat... More Details >>

    • No:21319
    • Release Date:2018/08/22 16:27
  • Switching between external operation and NET operation

    You can switch between external operation and NET operation by turning ON/OFF the terminal X66 (RM). You can switch while Pr.79 (Operation mode) is set to "6... More Details >>

    • No:21688
    • Release Date:2018/08/22 16:28