FAQ within [ FREQROL-F700 ]

261-270 of Total 295

prev 27 / 30page next
  • Easy setting mode

    If "HOLD" is displayed, the key lock mode enabled. Press the "MODE" key for two seconds. Then, change the setting of Pr.79 to "1". More Details >>

    • No:21350
    • Release Date:2018/08/22 16:27
  • Monitor indicator

    The first priority window of the monitor may be set to the current.When the current is displayed on the monitor (the unit is "A"), press "SET" to switch to t... More Details >>

    • No:21765
    • Release Date:2018/08/22 16:29
  • Adjustment of analog gain

    Use Pr.903 (Frequency setting voltage gain) for setting the FR-E500. For the 700 series, use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (... More Details >>

    • No:21689
    • Release Date:2018/08/22 16:28
  • NET operation mode

    Normally, the inverter starts up in the NET operation mode at power ON when Pr.340 is set to "10" and Pr.79 is set to "0". When it starts up in the PU operat... More Details >>

    • No:21319
    • Release Date:2018/08/22 16:27
  • CC-Link

    Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>

    • No:21833
    • Release Date:2018/08/22 16:29
  • Instruction manual

    For the Instruction Manual "Applied", fill in the request sheet which is included in the last part of the Instruction Manual "Basic", and fax it to the speci... More Details >>

    • No:21341
    • Release Date:2018/08/22 16:27
  • Switching between PU and NET operations

    Even after setting Pr.340 to "10", the change is reflected after resetting the power supply.Perform the power reset.Since changes to the communication parame... More Details >>

    • No:21696
    • Release Date:2018/08/22 16:28
  • Frequency setting

    The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>

    • No:21800
    • Release Date:2018/08/22 16:29
  • Operation mode setting value

    Set Pr.79 to "2" (external operation mode).    More Details >>

    • No:21818
    • Release Date:2018/08/22 16:29
  • Graph function in FR-Configurator

    Even the USB is used, FR Configurator requires at least 50 ms sampling time (for each monitoring item). In this case, since three types of data are monitored... More Details >>

    • No:21310
    • Release Date:2018/08/22 16:26

261-270 of Total 295