FAQ within [ FREQROL-F700 ]

261-270 of Total 296

prev 27 / 30page next
  • CC-Link

    If Pr.340 (Communication startup mode selection) and Pr.79 (Operation mode selection) are set so that the inverter starts CC-Link operation from power-on and... More Details >>

    • No:21840
    • Release Date:2018/08/22 16:29
  • CC-Link

    Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>

    • No:21839
    • Release Date:2018/08/22 16:29
  • CC-Link

    You can use the CC-Link type programming example for the FR-E500 as a reference.In the programming example for the FR-E500, the A series programmable control... More Details >>

    • No:21836
    • Release Date:2018/08/22 16:29
  • CC-Link

    Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>

    • No:21833
    • Release Date:2018/08/22 16:29
  • CC-Link

    You can use optional items, such as enclosure surface operation panel FR-PA07 and parameter unit FR-PU07.Use the PU connector of the inverter for connection.... More Details >>

    • No:21832
    • Release Date:2018/08/22 16:29
  • CC-Link

    Check if the master station uses CC-Link Version 1 and the FR-A7NC uses CC-Link Version 2. More Details >>

    • No:21831
    • Release Date:2018/08/22 16:29
  • CC-Link

    The FR-A7NC is designed for the FR-A700, FR-F700, and FR-F700P.The FR-A7NC E kit is designed for the FR-E700 with the dedicated cover. (Only the dedicated co... More Details >>

    • No:21830
    • Release Date:2018/08/22 16:29
  • CC-Link

    You cannot monitor the running frequency and conveyor speed (machine speed) simultaneously.The inverter does not have a function to output them simultaneously. More Details >>

    • No:21827
    • Release Date:2018/08/22 16:29
  • CC-Link

    Yes. Set the first monitor code in the lower 8 bits and the second monitor code in the upper 8 bits of RWwn.Set H6F to the first monitor code, and H70 to the... More Details >>

    • No:21824
    • Release Date:2018/08/22 16:29
  • Programmable controller

    The error LED on the master side of the programmable controller blinks (faulty station present).According to the SW80 station information, an error flag is a... More Details >>