FAQ within [ FREQROL-F700 ]
-
It cannot be avoided by using parameters. More Details >>
- No:21724
- Release Date:2018/08/22 16:29
-
The 75K or higher DC reactor is included in the 75K or higher inverter. The option cannot be purchased separately. More Details >>
- No:21252
- Release Date:2018/08/22 16:26
-
Input 4 words, output 4 words for version 1. 2, 4, and 8 times for version 2. More Details >>
- No:21874
- Release Date:2018/08/22 16:29
-
Not available. Differences between the parts supplied with the FR-A7NC and FR-A7NC E kit will result in improper installation. Use the FR-A7NC. Use the FR-A7NC. More Details >>
- No:21258
- Release Date:2018/08/22 16:26
-
If Pr.340 (Communication startup mode selection) and Pr.79 (Operation mode selection) are set so that the inverter starts CC-Link operation from power-on and... More Details >>
- No:21840
- Release Date:2018/08/22 16:29
-
Check if the master station uses CC-Link Version 1 and the FR-A7NC uses CC-Link Version 2. More Details >>
- No:21831
- Release Date:2018/08/22 16:29
-
Set Pr.55 (Frequency monitoring reference) of the first inverter to 70 Hz. More Details >>
- No:21257
- Release Date:2018/08/22 16:26
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26
-
The signals MRS and CS are required when the automatic bypass sequence enabled. More Details >>
- No:21187
- Release Date:2018/08/22 16:26
-
For the inverter, the option card FR-A7NC is necessary. More Details >>
- No:21897
- Release Date:2018/08/22 16:29